Four-Bolt Unstiffened End-Plate Moment Connections with 36-in.-Deep Beams for Intermediate Moment Frames

Authors

  • Maria A. Mercado-Celin
  • Matthew R. Eatherton
  • Thomas M. Murray

DOI:

https://doi.org/10.62913/engj.v61i1.1317

Keywords:

end-plate moment connection, intermediate moment frame, lateral-torsional buckling, beam net section fracture, moderately ductile section

Abstract

Previous testing has shown that four-bolt extended, unstiffened end-plate moment connections can be used with beams up to 24 in. deep and develop sufficiently ductile performance to satisfy seismic qualification. It is desirable to extend this depth limit to allow deeper beams for intermediate moment frames. Three moment connection specimens using built-up 36-in.-deep beams with a four-bolt extended, unstiffened end-plate moment connection were tested to determine if they satisfy the intermediate moment frame qualification criteria given in AISC 341-16 (2016a). The web of the specimens satisfied the moderately ductile section criteria for web slenderness, which is required for intermediate moment frames, but not highly ductile section criteria required for special moment frames.


All three specimens passed qualification criteria for intermediate moment frames (IMFs) as given in AISC 341-16 by retaining at least 80% of the nominal plastic moment strength through 2% story drift. The observed failure modes included lateral torsional buckling of the specimen, flange local buckling, net section fracture of the beam flange, and failure of the beam flange-to-beam web fillet weld. The results of these tests support current moderately ductile limits associated with lateral bracing and cross-section slenderness, given that the associated specimens reached IMF qualification criteria but not special moment frame (SMF) criteria. It was concluded that four-bolt extended, unstiffened end-plate moment connections satisfy intermediate moment frame requirements with a beam depth of 36 in. and that a modification is needed for beam web to flange welds in built-up sections near the moment connection.

Downloads

Published

01/01/2024

How to Cite

Mercado-Celin, M. A., Eatherton, M. R., & Murray, T. M. (2024). Four-Bolt Unstiffened End-Plate Moment Connections with 36-in.-Deep Beams for Intermediate Moment Frames. Engineering Journal, 61(1), 047–058. https://doi.org/10.62913/engj.v61i1.1317

Most read articles by the same author(s)

1 2 > >> 
| American Institute of Steel Construction